Circuit-breaker ( 2 )

HIGH VOLTAGE CIRCUIT BREAKERS :

ii) SF6 ( sulphur hexa flurried ) : 


In SF6 circuit breakers, sulphur hexafluoride (SF6) gas is used as the arc quenching  medium. The SF6 is an electro-negative gas and has a strong tendency to absorb free electron .The contacts of the breaker are opened in a high-pressure flow of sf6 gas and arc is struck between them. The conducting free electrons in the arc are rapidly capture by the gas to form relatively immobile negative ions. This loss of conducting electrons in the arc quickly builds up enough insulation strength to extinguish the arc the SF6 circuit breakers have been found to be very effective for high power and high voltage service .


iii) OCB ( oil circuit breaker ): 


Oil circuit breaker is such type of circuit breaker which used oil as a dielectric or insulating medium for arc extinction. In oil circuit breaker acure in the system the contacts of the breaker are made to separate within an insulating oil. When the fault the contacts of the circuit breaker are open under the insulating oil and an arc is developed between them and the heat of the arc is evaporated in the surrounding oil. The oil circuit breaker is divided into two categories 


1- bulk oil circuit breaker


2- minimum oil circuit breaker



ADVANTAGE and DISADVANTAGE of OIL CIRCUIT BREAKERS : 


ADVANTAGE :


--Transformer oil is good insulating materials which insulates both contracts

--Hydrogen gas has high diffusion rate

that's why, deionized the ionized particles



DISADVANTAGE : 


-- oil remains inflammable

       risk of fire hazards

-- Due to mixture of air and hydrogen gas

           can be explosion

-- When ionized particles started to deionized

carbon particles mixed in to oil


iv) ACBC ( air blast circuit breaker ): 



In this type of circuit breaker, shown in Fig , compressed air is used as the medium for closing or opening the contacts. As such there will be a high pitched blasting noise when the ABCB closes or opens. The type shown is a 110KV 3-phase breaker having all the 3-phases mounted on one air reservoir and has a single closing mechanism.



V) ELCB ( earth leakage Circuit breaker ) :


Earth leakage circuit breakers are the devices designed to provide protection against accidents by rapidly interrupting dangerous contact voltages which may be present in the faulty electrical equipment as a result of ground faults, insufficient insulation, insulation failure or misuse and sabotage. Basically the ELCBs are of two types, voltage operated ELCBs and current operated ELCBs

Over the years, it has been established that current operated ELCBs are much more reliable in operation, easier to install and maintain. Besides, there is no dangerous ageing of the protective system components involved, as in the voltage operated ELCBs, where the earth electrode resistance changes with time and hence the earth loop impedance does not remain constant over a period. This leads to dangerous touch voltages on the metal enclosures without being sensed by the voltage operated ELCBs, whereas current operated devices are safer as they operate on the principle of the vector sum of the line currents and the neutral current. Any current even in milliamperes which is not returning to the source through the neutral is assumed to be flowing through the earth or through any insulating body. This differential current is immediately sensed by the current operated ELCB which switches off the electricity supply, protecting the people from dangerous electrical shocks and the insulations from failing and inviting dangerous fires.

They also provide a high degree of protection against earth faults and fires. Fig 9 shows the circuit diagram of a residual -current earth leakage circuit breaker. The essential part of the ELCBs is a toroid type core transformer with two opposed windings called primary. One is connected in series with the line and the other in series with the neutral As far as there is no leakage current, the line current is equal to the neutral current and the magnetic flux produced by the two primary windings oppose and cancel each other. Thus the secondary winding which is connected to the trip (operating) coil does not induce any voltage.


SOME IMPORTANT QUESTIONS ANSWER FOR comparative EXAMS :


1.Arc in a circuit breaker behaves as-


Ans = A resistance decreasing with voltage rise across the arc


2. The main function of fuse is to-


ans= prevent excessive current


3. Directional relays are based on the flow of


ans= power


4. The voltage appearing across the contacts after opening of the circuit breaker is called


Ans= recovery voltage


5. Wave trap is used to trap waves of


ans= Higher frequencies


6. The reflection coefficient of voltage at the open circuited end of a transmission line is


Ans= 1


7. To reduce short circuit fault currents __ are used

Ans= reactor


8. For which of the following protection from negative sequence currents is provided-


a) transformer 


b) generators 


c) motors 


d) transmission line                    ANS=B


9. Which relay is preferred for phase fault on short transmission line


 a) Induction type


 b) reactance 


c) impedance 


d)none                                             Ans=B


10. Short circuit currents are due to which fault-


a) Single phase to ground 


b) phase to phase 


c) double phase to ground


 d)three phase


 e) all                                                    Ans=E


11. What will be the reflection coefficient of the wave if surge impedance) line is equal to load impedance?


Ans= zero


12. Which device will receive voltage surge first travelling on transmission line?


Ans=lighting arrestor 


13. Arc in a circuit breaker is interrupted at-


Ans= current zero


14. Overfluxing protection is recommended for-


Ans= Generator transformer of the power plant


15. Admittance relay is -


a) Impedance 


b) directional


 c)non directional


 d)non                                  Ans=B


16. The material used for fuse must have-


Ans = Low melting point and high specific resistance


17. A fuse is connected in-


Ans= Series with circuit


18. The inductive interference between power and communication line can be minimised by-


Ans= Transposition of both lines


19. A short circuit is defined by-

Ans= heavy current flow

20. A balanced 3phase system consists of -

Ans=Positive sequence currents only

21. The transient voltage that appears across the contacts at the instant of arc extinction is called-

Ans= Restriking voltage

22. Which relay is used for protection of motors against overload-

Ans= Thermal relay

23. Breaking capacity of a circuit breaker is usually expressed in terms of

Ans= MVA

24. In a circuit breaker the time duration from the instant of the fault to extinction of arc is known as-

ans = Clearing time

25. Which is a symmetrical fault-

Ans= Three phase fault

26. A differential relay responds to

Ans= Vector difference between two electrical quantities

27. Buchhols relay is used for protection against-

Ans= Internal faults in transformer

28. Buchhols relay is connected -

Ans= In the pipe connecting main tank of transformer and conservator

29. Merz price protection is used for

Ans = alternator

30. A lightning arrester provides-

Ans= A low impedance path between line and ground, during operation

31. Surge modifiers are used to

Ans= Reduces the steepness of wave front

32. Which of the following protective devices can be used against lightning surges- 

a) Lightning arrester 

b)horn gap 

c)surge diverter 

d) any of the these                       Ans=D

33. The over voltage surges in power system may be caused by-

 a) resonance 

b) switching 

c) lightning 

d) any of these                              Ans=D

No comments

Powered by Blogger.